Sign In | Join Free | My disqueenfrance.com |
|
Brand Name : Ningbo Suntech Power
Model Number : CHX(JZ) Series
Certification : ISO9001
Place of Origin : Ningbo,China
MOQ : One Unit
Price : Negotiable
Payment Terms : L/C, T/T
Supply Ability : 4sets / 2months
Delivery Time : 45~60 working days
Packaging Details : Export Standard Wooden Case With Fumigation Free
Test Principle : Variable Frequency Resonant Circuit
Usage : On-site AC Withstand Voltage Test For HV GIS Or Cable
Design Feature : Fast Installation And Fast Recycling , Container Type
Component : Test Reactor , V/F Power Source , Excitation Transformer , Voltage Divider
Test Frequency : 20~300Hz
Duty Cycle : 60mints
Test Accuracy : No Less Than 1.5%
Output Waveform : Good Sine Wave
Special For : On-site Test For 132KV GIS And Cable
Test Standard : IEC60060-1:2010;IEC 62271-203:2011 For GIS
High Light : resonant test set, high voltage testing of electrical equipments
Variable Frequency Resonant Withstand Voltage Test Set , Container Type HV Test Set With Resonance , Fast Testing
I. Application :
CHX-(JZ) container style series resonance test device fixes all the test equipment of series resonance test device in several containers, integration design of observe and control cabinet and complete test equipment,connecting test line and power distribution box aims to clipper transport, quick connect for test, convenient for maintenance and installation for the test equipment which greatly reduce labour intensity and suitable for field operation
II. Scope of Application
III. Kinds of solution
Note:part of them can be designed as hydraulic electric telescopic due to the size of the equipment.
Some parts of testers can be designed with compatibility
IV. Basic layout of containers
V. Technical Features and Advantage
VI. Main Components :
VII. General Technical Data:
Rated capacity: make by order
Rated voltage : made by roder
Rated current : made by order
Working power : supply single phase 380V,50Hz/60Hz
System quality factor value : Q ≥ 50
Duty cycle and temperature rise : after 60mints of rated operation, the winding temperature rise ≤ 65K
Noise: ≤ 65dB
Altitude: ≤ 2000m
Environment temperature: -25℃ ~45℃,Relative humidity ≤ 90% ,no condensation
![]() |